HV Copper Busbar Trunking/busduct System

Conductor material: Electrolytic copper or aluminum alloy conductors are used. Copper conductors meet the resistivity requirements of GB/T 3956-2008, and aluminum alloy conductors meet the mechanical strength standards of GB/T 29920-2013.

Insulation structure: The resin-cast shell has an IP66 protection level (in compliance with IEC 60529 standard), is filled with flame-retardant epoxy resin, and has a temperature resistance range of -40°C to 90°C.

Request a Quote

PRODUCTS DETAILS

Product feature description

◆Large-capacity power transmission design supports stable transmission and flexible distribution of kiloampere-level current

◆Optimized conductor structure effectively suppresses skin effect and achieves more than 98% energy transmission efficiency

◆Innovative heat dissipation structure design, operating temperature rise is 15-20% lower than industry standards

◆Adopt high-strength alloy materials, tensile strength ≥300MPa, bending radius ≤5D (D is outer diameter)

◆Dielectric strength of insulation layer ≥35kV/mm, passed the power frequency withstand voltage test (3.5kV/5min without breakdown)

◆Volume resistivity of special composite insulation material >1×10¹³Ω·cm, excellent arc resistance

◆Dynamic mechanical tests show that it can withstand 0.3g earthquake acceleration (equivalent to level 8 earthquake resistance)

◆Electromagnetic shielding effectiveness >60dB, protection level IP54, adaptable to harsh industrial environments

 

Certification Standards

IEC898/GB10963-1999: General specifications applicable to low-voltage circuit breakers, covering key indicators such as breaking capacity and temperature rise test.

CCC certification: According to GB 10963.1-2014 (equivalent to IEC 60898-1), it is required to pass short-circuit breaking capacity, durability and other tests.

CE certification: Complies with EN 41003-2008 and LVD directives, and conductor resistance, insulation withstand voltage and EMC test reports are required.

 

10kV Half-insulation pipe busway technical parameter

Rated current

Conductor specification

Rated peak withstand(KA)

Rated short time withstand current Icw(4s)KA

Temperature rise K

IP level

1600A

φ60x5

125

50

<65

IP54

2000A

φ60x8

125

50

<65

IP54

2500A

φ80x8

125

50

<65

IP54

3150A

φ80x10

125

50

<65

IP54

4000A

φ100x8

125

50

<65

IP54

5000A

φ100x10

160

50

<65

IP54

6300A

φ120x10

160

50

<65

IP54

1600A

φ80x8

125

50

<65

IP54

2000A

φ80x10

125

50

<65

IP54

2500A

φ100x8

125

50

<65

IP54

3150A

φ100x10

125

50

<65

IP54

4000A

φ120x10

125

50

<65

IP54

5000A

φ140x10

160

63

<65

IP54

6300A

φ150x10

160

63

<65

IP54

 

35kV Half-insulation pipe busway technical parameter

Rated current

Conductor specification

Rated peak withstand(KA)

Rated short time withstand current low(4S)KA

Temperature rise K

IP level

1600A

φ60x5

125

50

<65

IP54

2000A

φ60x8

125

50

<65

IP54

2500A

φ80x8

125

50

<65

IP54

1600A

φ80x8

125

50

<65

IP54

2000A

φ80x10

125

50

<65

IP54

2500A

φ100x8

125

50

<65

IP54

 