Air-Type Busway With 4P Or 5P And Rated Current 400A~6300A

Air type busway is suitable for AC three-phase three-wire, three-phase four-wire, three-phase five-wire system, frequency 50~60Hz, rated voltage up to 1000V, rated working current 250A~5000A power supply system, undertaking the task of power distribution, mainly used in modern workshops, plants and high-rise buildings.

Request a Quote

PRODUCTS DETAILS

product detail

Technical Parameters


Standard

IEC60439-1~2、GB7251.1~2、UL857

Rated working current(A)

250、400、630、800、1000、1250/1600

Rated peak withstand current(kA)

40、50、63、75、85、105、120

Rated short-time withstand current(kA)

20、25、30、40、50、55

The temperature rise of the conductive parts of the busway trough does not exceed the following values when the rated current is passed for a long time

Name

Maximum allowable temperature rise(K)

Connection terminals

60K

Metal housing

30K

Insulation surface

40K

Plug-in box parameters

Current(A)

32~1600

Rated working voltage(V)

400

Socket configuration

Standard 3 meters long linear section, can be set up in the front and back side of 1-10 plug interface


Current level(A)

Name

Air type busway/4P

Air type busway/5P

Dimensions

Wide(mm)

High(mm)

Wide(mm)

High(mm)

400A

168

76

168

76

500A

168

112

168

112

630A

168

101

168

101

800A

168

117

168

117

1000A

168

131

168

131

1250A

168

147

168

147

1600A

168

161

168

161

2000A

168

197

168

197

2500A

168

242

168

242

3150A

168

172

168

172

4000A

168

222

168

222

5000A

168

232

168

232

6300A

168

257

168

257




Advantage


Ultra High Strength


The shell of this series bus bar is made of one piece of steel plate (Ma Steel), which greatly improves the load capacity and can guarantee a load of 60kg in the center of bus bar at a span of 6m, and the center position of the plate shell is not shifted by more than 10mm when the non-uniform temperature changes.


Extremely safe and reliable


Adopting separated air insulation type, the safety clear distance and creepage distance between phases are much larger than the standard requirements.

Internal insulation parts are made of high-strength engineering plastic, which improves the resistance of busway to movement and thermal stability.

The special construction used for the joints prevents misuse of the installation.

Safety protection baffle is set at the socket, only when the protection baffle is pulled open, the plug box can be inserted. When the socket is not in use at ordinary times, the protective baffle can be pulled closed and sealed with lead to prevent the entry of dust or foreign objects at the socket, and to prevent misuse, so that the safety performance of the bus bar is greatly improved.

There is no need to disconnect the power when plugging in the box, because the ground wire is always connected and disconnected first.


Flexible wiring


The busway jacks are modular in design, with a large number of jacks reserved for the entire system. This ensures that loads can be connected to the busway units in a short path and that no changes to the busway system are required for the addition or movement of shop equipment or shop refurbishment.


Interchangeability


This series of busways is designed with seven current levels and uses only three levels of enclosures so that there is no need to change enclosures when the system varies capacity by adjacent current levels.


Extremely easy to install


The use of coupling with automatic compensation and single bolt clamping terminal with strong adjustability makes busway channel appear very convenient and flexible in the installation process, which greatly saves installation time.

Contact us

Please feel free to give your inquiry in the form below We will reply you in 24 hours

Leave YourMessage

Thank you! We will reply you via email within 24 hours.

Return